devices.esphome.io

Orno Triple Phase Energy meter OR-WE-517

Orno Triple Phase Energy meter OR-WE-517

Device Type: misc
Electrical Standard: eu
Board: esp8266

GPIO Pinout

PinFunction
GPIO03modbus RX
GPIO01modbus TX

Connection

Use RS485 adapter like this one: https://esphome.io/_images/rs485.jpg This one works with 3.3V and does direction switching automatically

esphome:
name: energie12
esp8266:
board: d1_mini
# Configure logging
# turn off logging because RX/TX pins used for modbus
logger:
level: DEBUG
baud_rate: 0 #off
# Enable Home Assistant API
api:
wifi:
ssid: "your_ssid"
password: "your_password"
# Enable fallback hotspot (captive portal) in case wifi connection fails
ap:
ssid: "Fallback Hotspot"
password: "xxxxxxxxxxxxxxx"
captive_portal:
uart:
id: mod_bus
rx_pin: GPIO01
tx_pin: GPIO03
# required for this meter type
baud_rate: 9600
parity: EVEN
stop_bits: 1
modbus:
id: modbus1
# flow_control_pin: 5
# not needed for my RS485 converter, but likely useful for ones with DE / RE pins
# uart_id: mod_bus
# maybe required when having multiple UARTs
modbus_controller:
- id: orno_we_517 # most likely similar devices will work as well
# the Modbus device addr
address: 0x1
modbus_id: modbus1
update_interval: 60s
command_throttle: 1s
# command throttle recommended to process only one command and result at a time
# number of 'registers/sensors' * command_throttle < update_interval
setup_priority: -10
sensor:
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Voltage_L1"
id: orno_we_17_modbus_voltage_L1
register_type: holding
address: 0x00E
unit_of_measurement: V
accuracy_decimals: 2
value_type: FP32
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Voltage_L2"
id: orno_we_17_modbus_voltage_L2
register_type: holding
address: 0x010
unit_of_measurement: V
accuracy_decimals: 2
value_type: FP32
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Voltage_L3"
id: orno_we_17_modbus_voltage_L3
register_type: holding
address: 0x012
unit_of_measurement: V
accuracy_decimals: 2
value_type: FP32
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Current_L1"
id: orno_we_517_modbus_current_L1
register_type: holding
address: 0x016
unit_of_measurement: A
value_type: FP32
filters:
- multiply: 0.01
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Current_L2"
id: orno_we_517_modbus_current_L2
register_type: holding
address: 0x018
unit_of_measurement: A
value_type: FP32
filters:
- multiply: 0.01
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "03_Current_L3"
id: orno_we_517_modbus_current_L3
register_type: holding
address: 0x01A
unit_of_measurement: A
value_type: FP32
filters:
- multiply: 0.01
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "03_Current_ALL"
id: orno_we_517_modbus_current_ALL
register_type: holding
address: 0x01C
unit_of_measurement: kW
value_type: FP32
filters:
- multiply: 0.01
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Leistung_L1"
id: orno_we_517_modbus_Kw_01
register_type: holding
address: 0x01E
unit_of_measurement: kW
value_type: FP32
filters:
- multiply: 1000
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Leistung_L2"
id: orno_we_517_modbus_Kw_02
register_type: holding
address: 0x020
unit_of_measurement: kW
value_type: FP32
filters:
- multiply: 1000
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Leistung_L3"
id: orno_we_517_modbus_Kw_03
register_type: holding
address: 0x022
unit_of_measurement: kW
value_type: FP32
filters:
- multiply: 1000
- platform: modbus_controller
modbus_controller_id: orno_we_517
name: "02_Hz_L1"
id: orno_we_17_modbus_Hz
register_type: holding
address: 0x014
unit_of_measurement: "Hz"
accuracy_decimals: 2
value_type: FP32
Edit this page on GitHub